Volume 13, Issue 1 (3-2023)                   J Health Saf Work 2023, 13(1): 1-17 | Back to browse issues page

XML Persian Abstract Print


Download citation:
BibTeX | RIS | EndNote | Medlars | ProCite | Reference Manager | RefWorks
Send citation to:

Ramezanifar E, Gholamizadeh K, Mohammadfam I, Mirzaei Aliabadi M. Reliability Assessment of Fixed Foam Systems of Storage Tank Based on Fuzzy Fault Tree Analysis. J Health Saf Work 2023; 13 (1) :1-17
URL: http://jhsw.tums.ac.ir/article-1-6799-en.html
1- Department of Occupational Health Engineering, Occupational Health and Safety Research Center, School of Public Health, Hamadan University of Medical Sciences, Hamadan, Iran
2- Department of Health, Safety and Environment Management, Occupational Health and Safety Research Center, School of Public Health, Hamadan University of Medical Sciences, Hamadan, Iran
3- Department of Health, Safety and Environment Management, Occupational Health and Safety Research Center, School of Public Health, Hamadan University of Medical Sciences, Hamadan, Iran , mirzaei@umsha.ac.ir
Abstract:   (1505 Views)
Introduction: Risk assessment is a scale for predicting reliability and can manage interactions between components and process variables. Moreover, the reliability of one component or barrier affects the overall risk of the system. Being one of the most critical safety barriers of the storage tank, the failures of Fixed Foam Systems (FFS) on demand can result in severe consequences. FFS, is of grave importance in decreasing the risks associated with fires and damages.
Material and Methods: This study aims to determine the probability of root causes related to FFS failure through Fuzzy Fault Tree Analysis (FFTA) to estimate system reliability. In conventional fault tree analysis, accurate data is usually used to assess the failure probability of basic events. Therefore, the introduced approaches were employed to quantify failure probabilities and uncertainty handling. Finally, system reliability was estimated according to the failure probability of the top event.
Results: The findings showed that 13 baseline events involved FFS performance. According to the results, failures of cable path and detection system (or resistance temperature detectors), set the activation switch (multi-position) incorrectly, and foam makers not continuously running are the three most critical basic events influencing the reliability of fixed foam systems. In addition, this paper estimated the system reliability at 0.8470.
Conclusion: The results showed that the FFTA could be used in matters such as reliability evaluation failure and risk assessment using experts’ judgment. This paper can also show the adaptation of the fuzzy approach to assess the failure probability of the basic event in the fault tree analysis (FTA).
Full-Text [PDF 1140 kb]   (1895 Downloads)    

Type of Study: Research |
Received: 2023/03/13 | Accepted: 2022/03/30 | Published: 2022/03/30

Add your comments about this article : Your username or Email: