Volume 3, Issue 2 (8-2013)                   J Health Saf Work 2013, 3(2): 47-58 | Back to browse issues page

XML Persian Abstract Print


Download citation:
BibTeX | RIS | EndNote | Medlars | ProCite | Reference Manager | RefWorks
Send citation to:

Aliabadi M, Hesam G, Rahimpoor R. Study of heating performance of radiant ceiling heating system and its impact on workers thermal comfort level of workers in typical industrial work shops. J Health Saf Work 2013; 3 (2) :47-58
URL: http://jhsw.tums.ac.ir/article-1-5064-en.html
1- Department of Occupational Hygiene, Faculty of public health, Hamadan University of Medical Sciences,
2- Department of Occupational Hygiene, Faculty of public health, Hamadan University of Medical Sciences, , ghasem_hesam@yahoo.com
Abstract:   (11414 Views)

Introduction: Introduction: Thermal comforts are one of the most human concerns in working as was as living environments in the past half century. Thermal comfort is the condition in which people are satisfied with the thermal environment, mentally. One of the new heating system employed in individual units is radiant heating system .The purpose of this study was to investigate the performance of radiant ceiling heating system and its impact on thermal comfort of workers.

.

Material and Method: In the present analytical-descriptive study, the designed radiant heating systems were investigated in two repair and maintenance units, in Hamadan gas pipeline operation center. Firstly, the environment parameters, witch impact thermal comfort, were measured before and after using radiant heating system, in both understudy units. Then, wind chill index, thermal comfort indices, PMV and PPD were calculated. In addition, PPD and PMV were determined, based on workers subjective feeling by a questionnaire distributed among 22 workers.

.

Results: According to the results, the radiant heating system in unit 1, has reduced the wind chill index by 42.3 Kcal/ m2.h, witch is not considered to be significant. In unit 2, wind chill index has been decreased by 109.3 Kcal/ m2.h, witch mean that thermal comfort has been changed from cold to an optimum environment. PMV n unit 1 went up by 37% after turning the system on, witch is equal to 17.24% increase in workers satisfaction. However, in unit 2, the workers satisfaction was 14.3% higher in comparison with unit 1.

.

Conclusion: Due to large space of these industrial units, producing appropriate heating by convection mechanism is too difficult and expensive. The results confirmed that if radiant heating system applied based on scientific design principles they could be effective in promotion of thermal comfort due to heating surrounding surface by radiant and also reducing fuel consumption.

Full-Text [PDF 424 kb]   (4672 Downloads)    
Type of Study: Research |
Received: 2013/12/10 | Accepted: 2013/12/10 | Published: 2013/12/10

Add your comments about this article : Your username or Email:
CAPTCHA

Send email to the article author


Rights and permissions
Creative Commons License This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.

© 2024 , Tehran University of Medical Sciences, CC BY-NC 4.0

Designed & Developed by: Yektaweb